House, design, repair, decor. Yard and garden. Do it yourself

House, design, repair, decor. Yard and garden. Do it yourself

» Chiller with air cooled and remote condenser. Drivers: Work Features and Types of Devices

Chiller with air cooled and remote condenser. Drivers: Work Features and Types of Devices

\u003e Production of refrigeration equipment\u003e Fluid cooling installations\u003e VACTEKH chillers and configuration options\u003e

Chillers with remote condenser

Equipment "With a remote condenser" It is used in case of the impossibility of placing equipment with a significant heat generation within the workshop or machine compartment (for an approximate assessment - heat dissipation in the condenser (in kW) is 30% higher than the cooling capacity of the chiller (in kW)). A chiller itself is installed in the heated room, and the air-cooled condenser is mounted on the roof, next to the building or on the building wall. For some eastern regions of Russia, where the temperature in winter is held for a long period of time at the level - 30 ... - 35c, this is the only option of the configuration of water-cooler installations with a cooling capacity of more than 50-100 kW. When ordering a chiller with a remote condenser, the customer comes with two modules: the refrigeration unit (chiller itself) and air cooling condenser. Depending on the performance of the installation, it is completed with remote condensers of our own production, the production of firms Searle (England) or HTS (Czech Republic).

If a chiller with a remote capacitor is operated in the winter period of time (at ambient temperature below 0 s), it is equipped with a winter start-up system representing a system of overhead valves in the freon circuit that allows you to turn on the chiller after a long-term parking at low ambient temperatures. All valves of the winter start system are embedded inside the refrigeration unit during its production.

(Chiller) is a refrigerator (refrigerator) for or other liquid. Refrigerator Designed for the selection of heat in the cooled medium at low temperatures, while the recovery of heat at high temperatures is a by-process. As part of a refrigerator, several functional elements: compressor (from 1 to 4), capacitor, electric motor, evaporator, refrigerant extension device or thermostatic valve, control unit.

Obtaining an artificial cold is based on simple physical processes:, condensation, compression and expansion of working substances. Working substances used in refrigeration units, referred to refrigerators.

Refrigerating machines vary:

  • according to the design (absorption, with a built-in or remote capacitor - condenser and infancharitors);
  • type of cooling capacitor (air or water);
  • connection schemes;
  • the presence of a thermal pump.

Benefits

  • Ease of operation - the specified parameters in each room in accordance with sanitary and hygienic standards are automatically maintained.
  • System flexibility - the distance between chiller and fan coils is limited only by the power of the pump and can reach hundreds of meters;
  • Economic advantage - reduced operation costs;
  • Environmental advantage - harmless cooling carrier;
  • Construction advantage - planning flexibility, minimum cost useful Square on the placement of the refrigeration machine, because it can be installed on the roof, the technical floor of the buildings, in the yard;
  • Acoustic advantage - low-noise execution of aggregates;
  • Safety - the risk of the bay is limited due to the use of shut-off valves.
Chillers VMT-Xiron can serve as a source of cold supply, but also in the reversal mode of a refrigeration or water cycle to work as a heat pump, which is in demand during the cold season.

Types of chillerov

Absorption type is a very promising area of \u200b\u200bdevelopment of refrigeration technology, which gets more and more widely used in view of a pronounced modern trend towards electrical conservation. The fact is that for absorption refrigeration machines, the main source of energy is not an electric current, but a chapper heat, inevitably arising in factories, enterprises, etc. and irrevocably thrown into the atmosphere, whether hot airAir cooled hot water and others.

The working substance is a solution of two, sometimes three components. The most common binary solutions from the absorber (absorbent) and refrigerant corresponding to the two main requirements for them are the most common: high solubility of the refrigerant in the absorbent and a significantly higher boiling point of the absorbent compared with the refrigerant. Wide use was obtained solutions of water ammonia (water-free refrigeration machines) and bromide lithium-water (bromistric machines), in which, respectively, water and lithium bromide are absorbents, and ammonia and water - refrigerants. The operating cycle in absorption chillers (see in the figure below) is as follows: in the generator to which the cam heat is supplied) boils the working substance, as a result of which a practically pure refrigerant rolls out, its boiling point is much lower than that of the absorbent.

Couples of the refrigerant enters the condenser, where it is cooled and condensed, giving his heat environment. Further, the resulting liquid is throtting, as a result of which is cooled when expanding) and is sent to the evaporator, where, evaporated, gives his cold to the consumer and follows the absorber. This is also served by an absorbent through the throttle, from which the refrigerant was swollen at the very beginning, and absorbs pairs, because we have noticed the requirement of their good solubility. Finally, the absorbent pump is pumped into the generator to the producer by the refrigerant, where it drops again.

The main advantages of absorption chillers:

  1. An ideal solution for creating trigeration in the enterprise. The trigeration complex is a complex that is currently allowed to reduce the cost of electricity, hot water supply, heating and cooling for the enterprise through the use of its own cogeneration power plant in conjunction with absorption chiller;
  2. Long service life - within 20 years, prior to the first overhaul;
  3. low cost generated cold, cold is produced almost free, because Asborption chillers simply utilize the excess heat;
  4. The reduced level of noise and vibration, as a result of the lack of compressors with electric motors, as a result - silent work and high reliability;
  5. The use of refrigeration / heating units with a fiery gas generator of direct action allows you to abandon the boilers that must be used in conventional installations. This reduces the initial cost of the system and makes absorption refrigeration machines competitive compared to conventional systems in which boilers and coolers are used;
  6. Ensuring maximum electricity savings during peak load periods. In other words, without consuming electricity for the production of cold / heat, absorption chillers do not overload the power supply of the enterprise even at the moments of peak loads;
  7. There is an opportunity to combine into steam district systems with an efficient refrigeration unit of the double effect;
  8. It is possible to distribute the load in conditions of maximum performance in cooling mode. The device copes with a critical load in cooling mode with a minimum electricity consumption due to the use of coolers with a fiery gas generator of a direct action or a generator with steam heating;
  9. Allows the use of emergency electrical generators of less power, since the consumption of energy in absorption refrigeration settings is minimal, if you compare them with electrical refrigerator installations;
  10. Safety for the ozone layer does not contain refrigerants that destroy ozone. Cooling is carried out without the use of substances containing chlorine;
  11. It is reduced to a minimum of the overall impact on the environment, as the consumption of electricity and gas causing the greenhouse effect is reduced and as a result of global warming.

Absorption Chiller is a car that produces chilled water using residual heat from sources such as steam, hot water or hot gas. Chilled water is made according to the principle of cooling: liquid (refrigerant), which evaporates at low temperatures, absorbs heat from its surrounding environment during evaporation. Clean water is usually used as a refrigerant, while the bromide lithium solution (LIBR) is used as an absorbent.

How do absorption refrigeration systems work

In absorption refrigeration plants, the absorbent, generator, pump and heat exchanger replace the compressor of the cooling system of the steam compressor (mechanical cooling). The remaining three (3) components discovered also in mechanical refrigeration systems, that is, an expansion valve, evaporator and a capacitor are also used in absorption refrigeration systems.

Stage of evaporation of absorption coolers

Refer to Figure-2 for a schematic explanation of the absorption cooling process. Like mechanical cooling, the cycle "begins" when the liquid refrigerant high pressure The capacitor passes through the expansion valve (1, in figure 2) to the low pressure evaporator (2, in figure 2) and collects a sump in the evaporator.

In this low pressure, a small amount of freon begins to evaporate. This evaporation process cools the remaining liquid refrigerant. Similarly, heat transfer from relatively warm process water to chilled currently refrigerant leads to the fact that the latter evaporates (2, in FIG. 2), and the resultar pairs is fed to the lower pressure absorber (3, figure 2). As technological water loses heat to the refrigerant, it can be cooled to significantly low temperatures. At this stage, the cooled water is actually obtained by evaporation of freon.

Absorption Stage Absorption Coolers

Refrigerant vapor absorption in lithium bromide is an exothermic process. In the absorber, the refrigerant "is absorbed" by the absorbing solution of lithium bromide (LIBR). This process not only creates a low-pressure region, which pulls a continuous flow of a pair of refrigerant from the evaporator to absorber, but also causes steam to condensate (3, in figure 2), since it releases the heat of evaporation provided for in the evaporator. It is warm, together with the heat of dilution arising when mixing the condensate of the refrigerant with an absorbent, is transferred to the cooling water and stands out in the cooling edge. Cooling water is a utility at this stage of cooling.

Regeneration of lithium bromide solution

As the lithium bromide absorbent sucks the refrigerant, it becomes more and more diluted, reducing its ability to absorb a greater amount of refrigerant. To continue the cycle, the absorbent must be re-concentrated. This is achieved by constant pumping down the diluted solution from the absorber to the low-temperature generator (5 in Figure 2), where the addition of residual heat (hot water, steam or natural gas) boosts (4, in Figure 2) refrigerant from the absorbent. Often this generator is used to utilize the spent heat from the factory. As soon as the refrigerant is removed, the reconnected solution of lithium bromide is returned to the absorber, ready to resume the absorption process, and the free freon is sent to the condenser (6, in figure 2). At this stage of regeneration, spent heat from steam or hot water is useful.

Condensation

Couples of refrigerant boiled in the generator (5, in Figure 2) returns to the condenser (6), where it returns to its liquid state when cooling water raises the heat of evaporation. Then it returns to the expansion valve, where the full cycle is completed. At the stage of condensation, the cooling water becomes useful again.

Various technologies for absorption chillers

Absorption chillers can be disposable, double or newest, which is a triple effect. Machines with one effect have one generator (see the scheme above, Figure 2) and have the value of COP less than 1.0. Two-effect machines have two generators and two capacitors and are more efficient (typical COP values\u003e 1.0). The triple effect machines add a third generator and capacitor and are most effective: the typical value of COP\u003e 1.5.

Pros and cons of the absorption refrigeration machine systems

The main advantage of absorption chillers is lower costs of electricity. Costs can be even further reduced if natural gas is available at a low price or if we can use a low-grade heat source, which otherwise is lost at the factory.

Two main lack of absorption systems - their size-weight, as well as their need for larger cooling towers. Absorption more and harder compared to electric chillers of the same power.

Parokompression of chillers are the most common type of refrigeration equipment. The generation of cold is carried out in a parocompression cycle, consisting of four main processes - compression, condensation, choke and evaporation - using four main elements - compressor, capacitor, regulating valve and evaporator - in the following sequence: working substance (refrigerant) in a gaseous state comes to The input of the compressor with pressure P1 (~ 7ATM) and the temperature T1 (~ 5 ° C) and shrinks there before the pressure P2 (~ 30atm), heating to the temperature T2 (~ 80 ° C).

Further, the freon follows to the condenser where it is cooled (as a rule, due to the environment) to the temperature T3 (~ 45C), while the pressure ideally remains unchanged, it remains actually for tenths of ATM. In the process of cooling, the freon condenses and the resulting liquid enters the throttle (element with high hydrodynamic resistance), where it is very quickly expanding. At the output, a pair-liquid mixture is obtained with parameters P4 (~ 7ATM) and T4 (~ 0C) entering the evaporator. Here Freon gives his cold to the flowing evaporator with a coolant, heating and evaporating at constant pressure (really, it will fall on the tenths of the atmosphere). The resulting cooled coolant (TX ~ 7c) is the final product. And he at the outlet of the evaporator has the parameters P1 and T1, which enters the compressor. The cycle closes. Driving force - Compressor.

Refrigerant and coolant

We particularly note the separation of similarities similar to the first look - refrigerant and coolant. The refrigerant is a working substance of the refrigeration cycle, in the process of which it can be in a wide pressure range, and also undergoes phase changes. The coolant (phase changes) does not change and serves to transmit (transfer) heat (cold) for a certain distance. Of course, it is possible to carry out an analogy, saying that the driving force of the refrigerant is a compressor with a compression ratio of about 3, and the coolant is a pump that increases the pressure of 1.5-2.5 times, i.e. The numbers are commensurate, but the fact is the fact of the presence of phase changes in the refrigerant. In other words, the coolant always works at temperatures below the boiling point for the current pressure, the refrigerant may have a temperature both below and above the boiling point.

Classification of parocompression chillers

By installation type:

Outdoor installation (built-in capacitor)

Such aggregates are a single monoblock installed on the street. It is convenient because it allows to exploit non-exploitable areas - roof, open areas on Earth, etc. Also this is a cheaper solution. At the same time, the use of water as a coolant is associated with the need for its plum for a winter period, which is inconvenient, therefore, non-freezing fluids are used, both new salt and traditional glycol solutions in water. In this case, it is necessary to recalculate the work of the chiller under each specific coolant. Note that all today's non-freezing solutions are 15-20% less efficient than water. The latter is generally difficult to surpass - highly hidden liquids heat capacity and density make it almost perfect coolant, if not such a high freezing temperature.

Internal installation (remote condenser)

Here the situation is practically reverse as compared with the previous option. The refrigerator consists of two parts - the compressor-evaporative unit and the condenser connected by the freon route. Sometimes quite valuable areas are required inside the building, while still it is necessary to place the outside to accommodate the condenser, the truth with noticeably smaller requirements both in the area and by weight. In the chillers of the internal installation does not arise problems using water. We mention a somewhat more power consumption of the compressor and increased pressure loss and due to the elongated track (from chiller to the condenser), which, by the way, is also limited to the compressor in length.

By type of condenser:

This is the most common option. The capacitor is a tubular-ribbed heat exchanger and is cooled by free outdoor air. This is cheap and easy to design, installation and operation. Perhaps, only large capacitor dimensions can be called a minus in view of the low air density.

Water cooling

However, in some cases the water cooling of the capacitor is used. In this case, the condenser is a plate, plate-ribbed or heat exchanger "Pipe in a pipe". Water cooling significantly reduces the dimensions of the capacitor, and also allows to realize heat recovery. But the resulting heated water (about 40 ° C) is not a valuable product, often it is simply sent for cooling in the cooling, again, giving all the heat of the environment. Thus, water cooling is really beneficial in the case of the presence of a consumer of heated water. In any case, water-cooled chillers are more expensive than with air, and the entire system is generally more complicated and in design and in installation.

Traditionally, cooling cooling towers in which water, heated in the condenser, is used to cool the refrigeration machine condenser, is sprayed through the nozzles in the flow of the moving outdoor air, and with direct contact with air cools to the temperature of the wet thermometer of the outer air, then entering the condenser. This is a pretty cumbersome device that requires special service, pumping the pump and another auxiliary equipment. Recently, the so-called "dry" cooling and coolers of the condenser are used, which represent the water-air surface heat exchanger with axial fans, in which the heat of water heated in the condenser is transmitted to air, the circulation of which through the heat exchanger provides axial fans.

In the first case, the water circuit is open, in the second case - a closed, in which it is necessary to install all the necessary equipment: circulation pump, expansion tank, Safety valve, shut-off valve. To prevent water freezing when the chiller is working in cooling mode at negative outdoor temperatures, a closed circuit is filled aqueous solution non-freezing fluid. When water cooling the heat capacitor, the condensation is also useless and promotes thermal pollution of the environment. In the presence of a heat source, such as a hot water supply system or a technological line, during the production of cold, it is possible to use the heat of condensation.

By type of vehicle of hydromodul:

Chillers of such a configuration are a monoblock, which includes a pumping group and, as a rule, an expansion tank. Obviously, manufacturers produce standard hydromodules most often than two modifications - with less and more powerful pumps that do not always satisfy the necessary requirement (usually their pressure may simply be lacking). In addition, the built-in hydraulicodul in the chillers of the outer installation will be located on the street, which can create problems in winter - the non-freezing heat carrier may thicken and in the first seconds of work the pumps are not able to overcome its viscosity and do not start. On the other hand, there is no need to look for a place for the pumping station, think over its layout, etc. Plus, there are no problems with automation - this is a very significant advantage of embedded hydraulic modules.

With remote hydrogen

The remote hydrogen is used, firstly, when there is not enough power of the built-in; secondly, if necessary (we note that one backup pump is allowed in the built-in hydraulic modules); Thirdly, if for any reason the internal installation of pumps is desirable. The system becomes flexible, and the length of the track is almost unlimited, because the pumps are very powerful. At the same time, there are ready-made pumping stations, including pumps and expansion tank and automation and compactly collected on the support frame.


By type of condenser fans:


Chiller options

- Function free cooling. Practically indispensable for chillers working in the cold season. There is a reasonable question, why use the park-compression cycle for cooling, if behind the already cold. The answer comes by itself - the coolant should be directly cooling with outdoor air. In the cooling system, the temperature schedule 7 / 12c is most common, and, it means, theoretically, street temperatures Below 7c is already possible to use free cooling. In practice, due to inexpensive, the scope is somewhat narrowed - at 0 ° C and below, the cooling capacity of frekuling reaches nominal values.

Body pump. - This is the mode of operation of Chiller "for heating." The parokompression cycle works several in other sequences, the evaporator and the condenser change their roles and the coolant is not cooled, but heats up. By the way, we note that Chiller, though a refrigerator, giving three times more cold than consumes, but it is even more effective as a heater - he will give it four times more than the electricity spent. The thermal pump mode is most common in public and administrative buildings, sometimes used for warehouses, etc.

Smooth start compressor - option that allows you to get rid of high starting currents exceeding workers by 2-3 times.

Typology Chillerov

The source of cold in the water-airing air conditioning systems is chiller - water protection refrigeration machine. There are chillers of various types depending on the method of cooling the condenser, the method of configuration: a monoblock or with a remote capacitor, with a built-in hydraulicodle of or without it, the operation mode (only cooling or cooling and heating). Manufacturers constantly upgrade the manufactured equipment based on the latest technological and design developments.

The nomenclature series of issued chillers in recent years has significantly updated significantly due to the widespread use of new more efficient types of compressors: spiral, single, twin-ventricular, which in the range of small, medium and large manufacturers gradually displaces piston compressors. A number of chillers with a built-in hydraulic module, including accumulating tank, expanded.

Planted and surface heat exchangers are often used as evaporators, which made it possible to reduce the dimensions of the aggregates and their weight. Recently, manufacturers have begun vibrating chillers on environmentally friendly Freons R407 ° C ,. Depending on the method of cooling the condenser, refrigeration units are divided into chillers with air cooled condenser and water cooling capacitor. The greatest application find chillers with air-cooled capacitor when the heat from the capacitor is removed by air, more often outdoor.

This method of removal of warmth requires installing it outside the building or the use of special measures that provide such a cooling method. Capacitor chillers are available in a monoblock design when all chiller elements are in one block, and chillers with a remote capacitor, when the main unit can be installed indoors, and the condenser cooled by the outer air is located outside the building, for example on the roof or in the yard . The main unit is connected to the air capacitor installed outside the building, copper freonofluids.

Monoblock chillers

Chillers with axial fans

Chillers in the monoblock design are manufactured with axial fans and centrifugal fans. Axial fans cannot work on the ventilation network, so chillers with axial fans should be installed only outside the building, while nothing should interfere with the flow of air into the condenser and emissions with its fans. Chillers with axial fans can be manufactured in various versions: 1 - standard, 2 - with full heat regeneration, 3 - with partial heat regeneration, 4 - to cool the aqueous non-freezing solution of ethylene glycol in the operating temperature range from + 4 ° C to -7 ° FROM.

The execution of chiller is possible with an additional way to regulate ho-loving performance. With the variants of the execution of chillers 1, 3 heat condensation is transmitted to the outer air and is irretrievably lost. With the variants of the execution of chillers 2 and 4, additional covering heat exchangers are installed, the duplicate capacitor completely in version R (the use of 100% heat condensation for water heating) or partly (use of 15% heat condensation for water heating).

Under option 4, the additional shell-tube capacitor is installed on the injection line after the compressor in front of the main air capacitor. Chiller configuration can be: ST-standard; LN - with a reduced level of noise, which is achieved by the device of sound-absorbing casing for the compressor and lowering the speed of rotation of the axial condenser fan compared with the standard configuration; En - with a significant reduction in noise level, which is achieved by a sound-absorbing casing device for a compressor, an increase in the area of \u200b\u200bthe live cross section of the capacitor for the air passage and the decrease in the rotation speed of the axial fan, as well as the installation of the compressor to spring anti-vibration supports, the use of flexible inserts on the discharge and suction refrigeration pipelines contour.

Requirements in the level of sound power generated by a working chiller with axial fans when installing outside the building may not be very high if there are no special requirements for noise levels in the development where this building is located. If such restrictions take place, it is necessary to calculate the sound pressure level in the noise room emitted by the chiller, and, if necessary, apply the chillers of a special configuration.

Chillers with centrifugal fans

Chillers with centrifugal fans are designed to install inside the building. Basic requirements for these blocks: Compactness and low noise associated with installation indoor. In chillers of this type, centrifugal fans with low rotational speed are used, most of the small and medium performance sizes have a spiral compressor, characterized by a low level of noise, in sizes with a sealed piston compressor it is placed in a special soundproofing casing. The side panels of such chillers have a sound-absorbing coating from the inside, it is possible to fit with the standard ST configuration, the SC configuration with a low noise level, where the semi-hermetic piston compressor is placed in a noise absorbing cover and there are flexible inserts on the discharge and suction pipelines of the refrigeration circuit.

When choosing this type of chiller and its placement, a free supply of cooling air to the chiller and a removal of air heated in the condenser should be ensured. This is carried out with the help of suction and injection ducts, while the ventilation network is formed, consisting of a centrifugal fan, an air heater (chiller capacitor), air ducts, intake and exhaust ventilation louvre lattices. The dimensions of the latter are selected based on the recommended speeds of air movement in the cross section of the lattices and air ducts.

It is necessary on the basis of the aerodynamic calculation to determine the pressure loss in the ventilation network. Pressure loss in the ventilation network should correspond to the pressure developed by the centrifugal fan, with the value of air flow, cooling capacitor. If the pressure of the centrifugal fan is less than pressure loss in the ventilation network, you can use a more powerful electric motor to a centrifugal fan by special order. Air ducts must be attached to the chiller using flexible inserts so that the vibration is not transmitted to the ventilation network.

Cyllars performance

Depending on productivity, chillers are equipped with three types of compressors: with spiral compressors for small (recently there has been shifted towards medium) performance, single compressors for medium and high performance by duvenous compressors for medium performance, sealed piston compressors for low performance and semi-hermetic piston compressors for average performance. Spiral and screw compressors as more efficient in a specific productivity range compared to piston replace gradually the latter. Chillers are produced in two versions: working only in the refrigeration machine mode and operating in two modes: a refrigeration machine and thermal. In chillers with air-cooled capacitor, in which work in the heat pump mode is provided, the reversal of the refrigeration cycle is provided, reversal of water circuit is provided in water-cooled chillers.

Chiller scheme with built-in hydraulic module

In an embodiment, the chiller block includes: a circulation pump on the return pipe, a membrane expansion tank, a watering valve for water, a sloping valve, a water filling unit, a pressure gauge, a differential pressure switch.

Energy Saving Technologies in Chillers

When developing modern climatic equipment, a particular importance is paid to the problem of energy saving. In Europe, the amount of energy consumed by equipment during the annual cycle of operation is one of the main criteria for making a decision when considering proposals submitted to the tender. To date, the essential potential for increasing energy efficiency is the development and creation of climate techniques that can act as rather cover the load schedule with constantly changing working conditions. For example, according to research conducted by Clivet, the oscillations of the average load on the air conditioning system during the season are up to 80%, while work at full capacity is necessary for only a few days a year.

At the same time, the daily chart of thermal excess is also uneven character with a pronounced maximum. Traditionally, in chillers with a capacity of 20-80 kW, two identical compressors set two independent refrigeration circuits. As a result, the unit is capable of working in two modes by 50% and 100% of its rated power. A new generation of chillers with a refrigerator from 20 to 80 kW allows three-stage performance regulation. In this case, complete refrigeration capacity is distributed between compressors in a ratio of 63% and 37%.

Chillers have a new generation both compressors are included in parallel and work on one refrigeration outline, that is, have a common capacitor and evaporator. Such a scheme significantly increases the energy conversion coefficient (KPE) of the refrigeration circuit when working with incomplete load. For such chillers at 100% load and outdoor temperature of 25 ° C KPE \u003d 4, and when working by 37% KPE \u003d 5. Considering the fact that 50% of the time chiller works with a load of 37% it gives significant energy savings.

To effectively implement a new decision on chillers, microprocessor controllers are installed, which allow:
  • monitor all operating equipment parameters;
  • adjust the set value of water temperature at the exit of chiller in accordance with the parameters of the outer air, technological processes or commands from the centralized control system (dispatch);
  • select the optimal power regulation step;
  • in the event of a real need to quickly and efficiently perform a defrost cycle (for models with a thermal pump).

As a result, it is automatically minimized by the short-term compressor inclusions, optimization of the operation time of compressors and adjusting water parameters at the exit of chillers in accordance with the real needs. As the tests were shown, on average, only 22 on the inclusion of compressors occurs during the day, while the compressor of conventional chillers turns on 72 times.

The average annual CPE of Chiller reaches 6, and energy savings, when using modern chillers instead of the usual, is 7.5 kW of an hour at 1m2 area of \u200b\u200bthe service facility per season, or 35%. Another important advantage that gives the use of new chillers is that it disappears the need to install bulky accumulating tanks, and the circulation pump embedded in the chiller body allows you to do without an additional pumping station.

As is well known, the type of compressors used is important for accuracy of the execution of the load of the cheillers. Traditionally, piston or screw compressors were used in high power chillers. The piston compressor has a large number of moving parts and, as a result, low efficiency due to large friction losses. In the course of operation of piston compressors, there is a high level of noise and vibration, and there is also the need for their regular maintenance. Screw compressors, in turn, have a complex design, and, as a result, a very high cost. The production of screw compressors turns out to be lowered.

Maintaining such compressors labor consuming and requires high personnel qualifications. In recent years, new compressors like Scroll appeared on the market, which are deprived of the characteristic drawbacks of piston and screw compressors. Scroll compressors have high energy efficiency, low noise and vibrations and do not need maintenance. This type of compressors is simple in construction, very reliable and, at the same time, is inexpensive. However, the performance of SCROLL compressors, as a rule, does not exceed 40 kW.

Application in modern chillers a plurality of small, but very reliable compressors like Scroll, as well as several refrigeration contours, made it possible to obtain a very "maneuverable" chiller, which is capable of producing the required refrigeration capacity with high accuracy. Obviously, the use of such chiller makes it unnecessary installation of the pumping station, and a wide selection of various productivity pumps built into the chiller housing solves all issues related to the circulation of chilled water. Very small launchers of new equipment should be highlighted. After all, the launch of small Scroll-compressors having low power consumption occurs alternately, in accordance with the increase in the load on the aggregate.

In all recent generation chillers, a modern microprocessor control system allows you to adjust the set value of the water temperature at the outlet of the chiller in accordance with the outdoor air parameters, technological processes or commands from the centralized control system (dispatch). From an economic point of view, the use of a large number of SCROLL compressors and the installation of a built-in circulation pump instead of a separate pumping station turns out to be a more profitable option than the use of expensive, powerful and complex semi-hermetic compressors.

Advantages and Disadvantages of Chillers

Benefits

Compared to Split systems in which the gas refrigerant circulates between the refrigerant and local nodes, the chiller-folkyl systems have advantages:
  • Scalability. The amount of fan coils (loads) on the central refrigerator (chiller) is almost limited only to its performance.
  • Minimum volume and area. The system of air conditioning a large building may contain a single chiller that occupies the minimum volume and area is saved. appearance Facade due to the absence of external blocks of air conditioners.
  • Virtually not limited distance between chiller and fan coils. The length of the tracks can reach hundreds of meters, since with high heat capacity of the liquid coolant, specific losses on the route meter of the track are much lower than in systems with a gas refrigerant.
  • Wiring cost. In order to communicate chillers and fan coils, ordinary water pipes are used, shut-off valves, etc. Balancing of water pipes, that is, leveling pressure and water flow rates between individual fan coils, is significantly easier and cheaper than in gas-filled systems.
  • Safety. Potentially volatile gases (gas refrigerant) are concentrated in a chiller, installed, as a rule, in air (on the roof or directly on Earth). Pipe wiring accidents inside the building are limited to the risk of the bay, which can be reduced by automatic shock reinforcement.

disadvantages

  • Chiller-Funkyl systems, in a strict sense, are not ventilation systems - they cooled air in each air-conditioned room, but do not affect air circulation. Therefore, to ensure the air exchange of the chiller-folkyl system, they are combined with air (roof) air-conditioning systems, refrigerating machines of which cooled the outer air and serves it in the room along a parallel system of forced ventilation.
  • Being more economical than the roof systems, Chiller-Fan Coil systems are certainly losing in the efficiency of VRV and VRF-systems. However, the cost of VRV systems remains substantially higher, and their limit performance (volumes of cooled rooms) are limited (up to several thousand cubic meters).
  • Some aspects of the design of cold supply
  • The refrigerator is an oven (all three dimensions significantly exceed the meter, and the length can exceed 10m) and heavy (up to 15 tons) equipment. In practice, this means a practically unconditional need to apply unloading frames for the distribution of chiller mass on large square With the choice of admissible points of support. Standard frames are far from always suitable for each specific case, therefore, most often requires special design.
  • Chiller VMT-Ksiron has 1-2 of the compressor, 1-12 fans, 1-2 pumps, which causes a whole range of negative vibrations, therefore, the chiller installation is certainly produced on the vibrationopores of the corresponding carrier ability, and connecting all pipelines through the vibrations of the corresponding diameter .
  • As a rule, connecting diameters of the chiller pipelines are smaller than the main pipe (more often on one, sometimes in two sizes), so the transition is required. It is recommended directly from Chiller to install the vibration and immediately follow-transition. Due to significant hydraulic losses, delete the transition from the unit is not recommended.
  • To avoid clogging of the evaporator from the coolant at the entrance to the chiller, the filter installation is mandatory.
  • In the case of a built-in hydraulic modulus, the exit from the chiller is required check valve To avoid water movement against the project.
  • To regulate direct and reverse streams, a jumper is recommended between them with a pressure drop control.
  • Finally, the documentation should always pay attention to which the heat carrier shows the data. The use of non-freezing coolant on average by 15-20% reduces the efficiency of the cooling system.

Hydraulic chiller scheme, hydraulic modulus

Scheme of the work of chiller with an air capacitor and a winter start-up system (monoblock design, without hydraulic modulus)


Specification

  1. Danfoss compressor
  2. High pressure relay cr
  3. Valve shut-off Rotolock
  4. Valve Differential NRD.
  5. Linear receiver
  6. Valve shut-off Rotolock
  7. DML filter dehumidifier
  8. Glass viewing SG.
  9. Solenoid valve EVR
  10. Valve thermostatory
  11. DAS / DCR DRAWER FILTER
  12. Low Pressure Relay Cr
  13. Valve shut-off Rotolock
  14. AKS temperature sensor
  15. FQS Fluid Duch Relay
  16. Electric shield
Danfoss

Scheme of the work of chiller with a remote air capacitor and winter start-up system (without hydraulic modulus)


Specification

  1. Danfoss compressor
  2. High pressure relay cr
  3. Valve shut-off Rotolock
  4. OUB oil separator
  5. Reverse NRV valve
  6. Valve Differential NRD.
  7. KVR condensation pressure regulator
  8. Crane ball GBC.
  9. Air cooling condenser
  10. Crane ballgbc.
  11. Reverse NRV valve
  12. Linear receiver
  13. Valve shut-off Rotolock
  14. DML filter dehumidifier
  15. Glass viewing SG.
  16. Solenoid valve EVR
  17. Solenoidal coil Danfoss
  18. Valve thermostatory
  19. Evaporator Plate Soldering Type in (Danfoss)
  20. DAS / DCR DRAWER FILTER
  21. Low Pressure Relay Cr
  22. Valve shut-off Rotolock
  23. AKS temperature sensor
  24. FQS Fluid Duch Relay
  25. Electric shield
The scheme is designed and provided by Danfoss

Scheme of the work of chiller with water cooling condenser and with condensation pressure regulation


Specification

  1. Danfoss compressor
  2. High Pressure Relay KP
  3. Valve shut-off Rotolock
  4. Water Cooling Condenser Plate Soldering Type B (Danfoss)
  5. Valve waterproining WVFX
  6. DML filter dehumidifier
  7. Glass viewing SG.
  8. Solenoid valve EVR
  9. Solenoidal coil Danfoss
  10. Valve thermostatic TE
  11. Evaporator Plate Soldering Type B (Danfoss)
  12. DAS / DCR DRAWER FILTER
  13. Low Pressure Relay KP
  14. Valve shut-off Rotolock
  15. AKS temperature sensor
  16. FQS Fluid Duch Relay
  17. Electric shield
The scheme is designed and provided by Danfoss

Scheme of hydrogen for chiller with one pump

Specification:

  1. Thermally insulated open-type capacity
  2. Pump
  3. Crane ball
  4. Collapsible connection
  5. Manometer
  6. Exit to the consumer
  7. Water inlet
  8. Bypass valve
  9. Filter rough cleaning
  10. Driver control relays
  11. Visual fluid control

What is Fan Coil: the principle of operation and guidance on the choice of device

Fan coil is an internal unit of the air-conditioning system of chiller-funkyl, capable of cooling or heating the air entering it. It is used to maintain the premises of the necessary microclimate throughout the year. This article discusses the principle of operation of such devices, their varieties, as well as the main advantages and cons.

Fan coil, which is also called a fan closer consists of two main elements: heat exchanger (radiator) and fan. In many models there is also a coarse filter - it prevents dust and dirt from entering the case. The equipment should be located indoors and is connected to the chiller (machine, cooling or heating fluid for transmitting thermal energy) using a pipeline network.

According to the principle of operation, fankyl is very similar internal block Split systems. The main difference lies in the coolant: instead of the refrigerant, the fan closer uses conventional water or non-freezing solution. The liquid cools or heats the incoming air, which is brought to the desired temperature and returns to the room. The condensate arising from this is discharged into the street or into the sewer with the pump.

As in the case of heating radiators, in one room, several fan coils are often installed - the required amount depends on the power of the devices and the room area. In addition, they can connect to supply ventilationthat allows you to use devices in mixed mode (mix the air obtained from the inside with fresh).

Temperature control is performed using an electronic system control unit, temperature sensors and various valves. In complex air conditioning systems, central air conditioners are also used that are responsible for cleaning and moisturizing the incoming air.

Types of chiller-funk systems

There are two main types of chiller-funk systems:
  • Single-room system. It is used mainly to maintain the premises of a large area with a uniform heat distribution, since all single-mounting fan coils connected to it are heated and cooled at the same time.
  • Multiserial system. Fan coils with double-circuit heat exchangers, which allows you to separate the flow of cold and hot water. Devices in such a system can simultaneously provide different air temperatures in different rooms.

Varieties of fan coils

All fan closers work on one principle - the devices differ only by the installation method. You can select four main types of fan coils:
  • Cassette;
  • Outdoor;
  • Wall;
  • Channel.
Each of the listed types is considered in detail below.

This type of devices is often used in air conditioning systems for offices or retail premises with high suspended ceilingsBecause they can be mounted in them. Cassette fan coats are produced in the following varieties:
  • Single-threaded (air is produced from the device in one direction);
  • Two-flow (from the device there are two air flows in different directions);
  • Four-way (models of this type produce four air flows, which makes them the best choice For air conditioning of the premises of a large area).

The simplest installation of the type of fan coil with an external case, which is attached to the floor. The most efficient location for the floor block is in front of the windows, since the air flows overlooking it are sent to the ceiling, creating an effective heat vest. Such funkowns can be supplied with both integrated in the device and remote controls.

Like outdoor blocks, wall fan coils are protected by decorative housings. They quickly mounted on the wall in any suitable place premises. Most often they are installed above the door. Almost all wall blocks are equipped with convenient remote controls.

Unlike wall or floor blocks, channel fan coils do not have housings - they are installed directly into ventilation mines. The devices of this type are used primarily for cooling or heating air in spacious rooms in need of high-performance air conditioning systems (shopping grounds, cinemas, entertainment centers, industrial workshops, etc.).

How to choose Fan Coil

When choosing a fan coil, the following device parameters should be taken into account:
  • Type (cassette, outdoor, wall or channel);
  • Power (the minimum indicator in watts can be obtained, multiplying the area of \u200b\u200bthe air-conditioned room per 100);
  • Energy efficiency (relevant only for large air conditioning systems, since fan coat consumes enough electricity);
  • Noise level (it is recommended to use devices with quiet fans, the noise level of which does not exceed 60 decibels).

Advantages and disadvantages of fan coils

Chiller-Fan Coil systems are popular due to a number of advantages compared to traditional split systems. Among the advantages can be allocated:
  • Scalability. The distance between the blocks in Split systems does not exceed 15 meters due to the refrigerant used in them. At the same time, the distance between Chiller and Fan Coil may exceed hundreds of meters, which makes it easy to expand the system if necessary.
  • Universality. Unlike air conditioners in standard split systems, fan coils are able to operate without stopping all year round.
  • Safety. Fan coils are much safer in comparison with a gas refrigerant used in split-systems.
Unfortunately, Fan Coils have disadvantages. These include:
  • Large system sizes. Due to the impressive dimensions of the chiller-funk system, its installation is appropriate only in spacious buildings.
  • Poor filtering quality. Fan coil filters for cleaning air copies with their task much worse than analogues in split systems.
  • High complexity of installation. Due to the large size and weight of Chiller-Funkyl systems, a lot of time and effort leaves for their installation.

Drivers: Work Features and Types of Devices

Drikeler, or is a fan apparatus used to cool the coolant by blowing out the street air. It is used both in small air conditioning systems - chiller fan coil and on large industrial enterprises. On this page you can find basic information about drivingkells, as well as a list of the most famous manufacturers of these devices.

Principle of operation Driver

The design of the driver includes three main nodes:
  • Plate heat exchanger. May have a V-shaped, horizontal or vertical form. Most often made from aluminum or copper. Efficient heat transfer is ensured due to the high number of edges, and, as a result, a large area of \u200b\u200bthe heat exchanger surface.
  • One or more fans. Most dripers are equipped with axial cooler impellers with radius from 200 to 350 mm. In large devices with V-shaped heat exchangers, the use of fans with a diameter of up to 1000 mm is allowed. Besides, in industrial systems High performance cooling can be used centrifugal fans.
  • Protective and regulating automatic equipment responsible for maintaining the required coolant temperature and changing the number of fan speeds.
  • Heated heat carrier (ordinary water or non-freezing solution) is supplied to the input of the driver, where its temperature is reduced to the outdoor air temperature. The cooling level can be adjusted by changing the number of revolutions of the fans. The fluid supply is performed using a circulation pump. After that, the cold coolant is supplied back to the cooled equipment, and then the cycle is repeated.

Advantages and disadvantages of dry gradies

Drives have a number of advantages. These include:
  • High energy efficiency;
  • Environmental safety (energy carrier circulates on a closed contour, and, as a result - does not evaporate, while maintaining the level of air humidity at the same level);
  • Easy installation, operation and service;
  • Low cost of equipment;
  • Simplicity of scaling (new blocks are easily added to the existing cooling system);
  • When working with dripers, any non-freezing solutions can be used.
At the same time, the driveculations have several significant drawbacks:
  • The performance of devices depends on the temperature of the outdoor air (problems are possible during periods of peak temperatures in winter and summer);
  • Drivers consume more electricity in comparison with standard evaporative hotkeys.

Scope of Drikeler

Due to good energy efficiency and low cost, the driver is popular for a number of applications. They can work both independent and as auxiliary equipment together with refrigerators. In particular, dry cooling towers are used:
  • In production in need of large volumes of the coolant;
  • In industry for cooling coolants in refrigeration and casting equipment, as well as heat removal from extruders, machine tools and generators;
  • In construction to reduce the temperature of refrigeration and electric generators;
  • For free cooling of air in public and industrial buildings (Fryriculing).
  • A large range of models and configurations of drivecleers allows you to choose a setup with suitable characteristics for any operating conditions, so every year their popularity is only increasing.

Large premises like entertainment or shopping centers, hospitals, hotels, manufacturing workshops and warehouses need a special system of air conditioning. It should be closely related to the operation of heating and ventilation systems, and at the same time it is desirable that it does not simply cooled air, but also moistened it or dried depending on the characteristics of the building. And best with such tasks today, air conditioning systems built on the basis of chillers are coping.

What does such a system give?

Chiller- or special refrigeration station - it is considered one of the most effective types of climatic equipment.which allows you to create optimal temperature and humidity conditions in any room. Its main function is cooling water, after which the pumping plants transport cold water through pipelines inside the building. At the same time, chillers can be the most diverse, but the system built on their base always has a mass gain:

  • she gives Maximum efficient cooling (or heating, if necessary),
  • she is economical - Chillers consume not too much electricity compared to other types of climatic equipment,
  • she is Not too expensiveo - most of all the user will spend only when the air conditioning will develop - this is the most energy-intensive part of the entire project, but it will quickly pay off,
  • she is multivariate - depending on the needs of the building and its inhabitants, you can choose the most different types Equipment equipped with a whole complex of special elements.

What are chillers?

There are found on sale different variants These aggregates, but only 6 varieties are considered basic.

1. Chiller equipped with a capacitor air cooling function.

As a rule, such equipment works on water, which acts as a cold sapper. This option is considered very economical and at the same time light in terms of design and subsequent installation, but air-cooled chillers have a number of shortcomings. Among them:

  • the possibility of work only at a positive temperature,
  • no adjustment high level sound pressure (its indicators are often excavated for 62 dBA),
  • the possibility of complete defrosting chiller if the water was fused not completely or not on time.

2. Chiller, equipped with a capacitor air cooling function in an external installation and working with non-freezing fluids.

As a rule, glycol acts as a heat exchanger and the farmers in this situation, but it may be water. Such a refrigeration station operates in a chart of 5/10 degrees, and the cooled water after the heat exchanger is characterized by parameters 7/12 degrees.

The advantages of this system are as follows:

  • the user does not need to empty the hydraulic system every season, and then fill it again,
  • chiller's evaporator never defams
  • the system is capable of working even with negative temperature outside,
  • in winter, such a system can be integrated with dry cooling towers for free air cooling.

On the other hand, similar chillers also have drawbacks. Among them:

  • fairly high price (compared to the previous model they cost about 30% more expensive),
  • higher electricity consumption (at the expense of glycol),
  • more low temperature coolant,
  • the presence of a second hydraulic circuit,
  • the need to use additional automation, preventing the defrosting of the heat exchanger, when the system is first started in the winter after a long downtime.

3. Chiller equipped with built-in cooling towers.

This equipment allows you to realize free cooling in cold seasons, and the automation independently chooses the optimal mode of operation - the operation of only cooling towers, the operation of the compressor only or the mixed mode. This allows you to achieve maximum economy of electricity, which makes such a system very economical and allows the user to quickly recoup the costs of it.

Another advantage of this option is that the refrigeration station with such equipment can be used without intermediate heat exchangers.

4. Chiller equipped with a remote condenser.

The system can effectively serve in certain conditions, but in most cases it will be characterized only by disadvantages:

  • such a chiller costs 30-40% more expensive than the first species,
  • the system can not work all year round in the regions with a cold climate,
  • free cooling can be achieved only if the system will work solely on this function,
  • there should be a small distance between the chiller and the condenser, not exceeding 30 m,
  • the system contains too much freon volume,
  • to install such a chiller, you will need exclusively professionals with the highest qualifications.

5. Chiller, equipped with a capacitor liquid cooling function, as well as dry cooling towers.

Equipment is considered to be not cheap, but it has many advantages:

  • such chiller has high energy efficiency,
  • the threat of defrosting the station is completely absent,
  • the system can work all year round, withsting temperatures up to -40 degrees,
  • chiller works almost silently,
  • the system is reliably protected,
  • the equipment can be installed on the roof, and the load on the roof will be minimal,
  • with minimal cost, you can set the additional function of free cooling,
  • the distance between Chiller and Cooling Caulne may be unlimited,
  • chiller does not need difficult seasonal service.

However, this technique will be about 60% more expensive than the first option.

6. Centrifugal chiller or water-cooled station having a centrifugal compressor.

The equipment is considered very effective, with the lower the temperature of the coolant, the higher the efficiency of the chiller. In order to increase it additionally, you can use an evaporative cooling tower, which will maintain water temperature at 30 degrees. This option is perfectly suitable for large buildings that need high-power systems.

At the same time, one more important advantage of such a system should be noted - the capital costs of it are small. But, on the other hand, there are disadvantages - the circuit of cooling water in such a chiller must constantly focus, and the minimum equipment performance will actually be 30% of the nominal indicator.

7. Absorption gas chiller equipped with water cooling function.

As a fuel, liquefied gas can be used on this equipment - imported or obtained from the gas pipeline (a reliable connection must be performed to install such a chiller to the gas pipeline). Also, this type of refrigeration system should be completed from evapultational cooling towers.

If the equipment is connected correctly, it will demonstrate excellent advantages:

  • minimum of the relative cost of energy consumed,
  • high payback,
  • the ability to generate heat in winter for heating the room and hot water supply.

At the same time, the capital costs of this type of equipment will be sufficiently high, and the minimum cleaner performance will be about 25% of the nominal indicator. Also, such equipment needs to feed the cooling water circuits.

What to choose?

Considering all these options, it is enough just to weigh everything as opposed, and you can approximately imagine what version of Chiller would be arranged. However, the final choice should be done taking into account the specifics of the entire object and your personal wishes and requirements. In particular, it will be necessary to take into account:


  • cost and main costs of electricity,
  • the connection price of additional electrical capacity,
  • price on network natural gas,
  • climate features in which you live
  • the desired payback period of equipment,
  • the possibility of using evaporative cooling towers,
  • the ability to install the refrigeration station and its elements both inside the building and outside,
  • features of the operational characteristics of the station at partial loads for a year,
  • the parameters of the cooled fluid and your requirements for them,
  • cost of the maintenance of Chiller during the year (the price of materials and work of specialists during the year),
  • service life.

For example, if you need to cool the server, be sure to note that the cooling capacity of the equipment must be at least 1 thousand kW, the cost of connecting additional energy will be 1.5 TC. Dollars / kW, and the minimum outdoor temperature will be up to - 40. At the same time, the technique will work all year round and the round day, and the gas will not be used.

Given this data, the optimal chiller option for the server will be free cooling system (Chiller No. 5) or chiller with built-in cooling towers (No. 3). The latter will be 20% cheaper when buying, and the first will be more economical subsequently. However, in any situation, all investments in such a system (with an equal value of maintenance and the same amortization) will be 5-7 years, after which they will give excellent savings. But if you need to connect additional electrosals (at the level of about 100 kW), the first option will definitely be more preferable from the point of view of the economy.

Similarly, chillers should be selected for any other premises. And only spending all accurate calculations and comparing the technical task with different types of stations that you could choose, you can choose the optimal climate technique.

Chillers have long been used to equip air conditioning systems. The area of \u200b\u200btheir use is quite wide: from offices and private houses, to medical institutions and large industrial workshops. Such popularity of the installation was won by high efficiency, convenience of operation, a variety of design options.

Depending on the installation site of the heat exchanger, chillers can be monoblocks (the chiller itself and the capacitor itself are in one case) or with remote condenser block. It is more likely to prefer a solid design, which also includes a pumping station. The most common option - systems with air cooling condenser. This design is mounted on the street to provide a full air flow to the heat exchanger.

When apply a remote capacitor?

There are situations where the chiller and heat exchanger is required. If the installation is used in the warm season, it successfully functions in the usual modification. But if the air temperature decreases and reaches negative values, the possibility of facing the equipment due to the freezing of water increases. To avoid this, water is removed from the system, and the chiller is subjected to conservation.

When it is necessary to ensure the continuous operation of the cooling equipment, the water is replaced by more expensive at the cost of non-freezing fluid. The above procedures are quite laborious and costly financially planned, as they must only be performed by professional workers who have the appropriate experience.

The task is greatly simplified if it is not a monoblock chiller, but equipped with a remote condenser. In this case, you can do without draining or replacing water to another liquid. The chiller and the pumping station are placed in a separate room, which is heated, and the heat exchanger is carried to the street, as it still requires a tributary of a large amount of air.

The principle of operation of the installation and its equipment does not change. The main elements of the chiller will be:

  • Compressor block.
  • Evaporator.
  • Heat exchanger.
  • Throttling device.

The disadvantage consists only of the need to create a highway connecting the cooling unit and a condenser. It is also necessary to take into account the difference in the height between blocks. Therefore, when choosing equipment, you should pay attention to these two parameters and determine in advance the convenient place of installation.

Chiller in the Smart Treding catalog will not be difficult, you can always count on the help of qualified managers, which not only recommend high-quality equipment at a bargain price, but also organize delivery and professional installation.